CERTIFICATE OF CONFORMITY INTERGAZSERT
Flare units are designed for emergency and continuous combustion of associated petroleum gas and natural gas or other combustible gases on gathering sites, treatment of oil&gas, as well as at oil refineries and chemical plants.
Upon customer request the Flare units can be delivered with:
1) with separate risers for high- and low-pressure gas combustion (FU type);
2) combined - with two or more risers (FCU type);
3) complete with lifting gears to bring risers to a horizontal position for repair or replacement of flare tips (UFOS type);
4) complete with lifting gears for lowering flare tips (UFO type);
5) open and closed surface flare systems.
Mobile flare units on the chassis or skid are also available for manufacturing.
Flare units are developed and manufactured as per TU 28.99.39-003-20676863-2017.
Designation sample for ordering of a product – flare unit FCU-1,0-HL1 TU 28.99.39-003-20676863-2017, where:
1,0 – amount of gas discharged, million m3/day;
FCU - combined flare unit;
HL1 - climatic modification.
Technical specifications |
|
Motive fluid |
natural, petroleum gas and other combustible gases |
Capacity for gas, thousand nm3/day |
from 1 to 24 000 |
Fuel gas consumption for pilot burners, nm3/h |
1,5÷2,0 |
Riser diameter, mm |
from 150 to 2000 |
Flare unit height, m |
from 10 to 150 |
Service life, not less than (years) |
30 |
Parameters |
Types |
|||||||
FU, FCU, UFOS, UFO |
||||||||
Amount of gas discharged, million m3/day |
From 0 up to and including 0,5 |
Over 0,05 up to and including 0,1 |
Over 0,1 up to and including 0,2 |
Over 0,2 up to and including 0,7 |
Over 0,7 up to and including 1,0 |
Over 1,0 up to and including 1,5 |
Over 1,5 up to and including 2,0 |
Over 2,0 up to and including 20 |
Main riser diameter D2, mm |
150 - 300 |
150 - 400 |
150 - 400 |
200 - 800 |
400 - 1000 |
500 - 1000 |
500 - 1400 |
700 - 2000 |
Riser height, H, m (for sulfur-containing gases) |
10 or more (30 or more) |
10 or more (30 or more) |
10 or more (30 or more) |
20-30 (30 or more) |
35 or more |
40 or more |
40 or more |
50 or more |
Number of pilot burners, pcs. |
1 |
1 |
1 |
2 |
2 |
3 |
4 |
4 |